
SECTION 9: WIRING AND ELECTRICAL INFORMATION
27 of 85
SECTION 9: WIRING AND ELECTRICAL INFORMATION
9.1 Electrical Supply
A 230 V 50 Hz 1 Ø supply is required for all heater
Models 015 to 030 connected to the heater terminals
L1, N and Earth.
Standard models 040 to 0100 and all High Flow
models require a 400 V 50 Hz 3 Ø and neutral
supply connected to the heater terminals L1, L2, L3,
N and Earth.
All heaters and controls must be correctly earthed.
All external wiring must comply with the relevant IEE
and local regulations and be carried out by a
qualified electrician.
Polarity "L & N" must be correct. The voltage
between neutral and earth should be 0 and never
exceed 15 volts.
An isolator with a contact separation of at least 3
mm (.12
") on all poles should be installed adjacent
to the heater, but not attached to it, to disconnect all
supplies to the heater and where necessary to
isolate the remote control panel.
9.2 Remote Controls
The heater is designed to be operated by controls
installed remotely from the heater. See Page 28,
Section 9.3. through Page 39, Section 9.14.
9.2.1 Burner Controls (Thermostat)
Controls to operate the burner must be voltage free
contacts connected between terminals 2 and 3 of
the main terminal block.
9.2.2 Positioning Room Thermostats or
ROBERTS GORDON
®
Control
A room thermostat or Roberts-Gordon Europe
Limited control should be mounted on a wall or
column at a height of approximately 1.5-1.8 m (5'-6')
from the floor to measure the ambient temperature.
It should be clear of both cold draughts and the
direct path of warm air from the heater.
9.2.3 Remote Frost Thermostat
When required, connect to terminals 2 and 3 in the
main terminal block.
Locate the thermostat within the heated space
adjacent to the most vulnerable equipment that
requires protection.
See Page 28, Section 9.3 through Page 39, Section
9.14.
9.2.4 Controls for High/Low Burner Operation
For heaters with a high/low burner, the controls will
need to provide two stage signal to operate these
burners. This is best provided by a two stage
thermostat.
The thermostat may control the heater outlet
temperature if the heater is designed for a duct
distribution system or the room temperature.
The site wiring will be across terminals 2 and 3 for
any time control and the on/off function of the burner
(stage two), and across terminals 7 and 8 for the
high fire (first stage) setting.
The b
urner will then operate as follows:
Temp. from cold up to the 1st set point..................
............................................ Full fire at max. rate
Temp. above 1st set point up to 2nd set point........
............................................ Low fire at min. rate
Temp. above 2nd set point ...............................Off.
9.2.5 Remote Fan Controls
The fan will operate automatically providing there is
a constant 230 V supply to the main terminals.
A switch or control wired between terminals L & 1 in
the terminal block will allow external control of the
fan(s).
The fan may be controlled to operate continuously
from an external control, with the burner cycling on
and off, providing that the fan run-on at close down
is not impaired.
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be
required to disconnect electric from
equipment.
Equipment must be properly grounded.
Failure to follow these instructions can result
in death or electrical shock.
Komentarze do niniejszej Instrukcji